Home Wiki Electricity & Electrons Cable & Wire Tables — Quick Reference
Electricity & Electrons

Cable & Wire Tables — Quick Reference

Why you need these tables

An undersized wire doesn't give you "weaker electricity" — it gives you heat. Heat destroys insulation, and failed insulation means a short circuit or a fire. Picking a cable cross-section isn't a detail; it's a safety decision.

This is a quick-reference page: open it on site, take the number, get back to work. The tables follow IEC 60228 (conductor resistance) and IEC 60364-5-52 (current-carrying capacity).


1. Conversion table: AWG ↔ mm²

American and Chinese drawings use AWG; European and Syrian specifications use mm². This table translates between them.

AWG Area (mm²) Diameter (mm) Typical use
30 0.05 0.255 Winding wire, fine electronics
26 0.13 0.405 Signal cable, internal USB
24 0.20 0.511 Networking (Cat5/6), signals
22 0.33 0.644 Control panels, sensors
20 0.52 0.812 Signal circuits, small relays
18 0.82 1.024 Light fixtures, control
16 1.31 1.291 ≈ 1.5 mm² — lighting
14 2.08 1.628 ≈ 2.5 mm² — socket outlets
12 3.31 2.053 ≈ 4 mm² — medium loads
10 5.26 2.588 ≈ 6 mm² — heaters, A/C
8 8.37 3.264 ≈ 10 mm² — sub-feeds
6 13.3 4.115 ≈ 16 mm² — sub-panels
4 21.2 5.189 ≈ 25 mm² — main feed
2 33.6 6.544 ≈ 35 mm²
1/0 53.5 8.252 ≈ 50 mm²
2/0 67.4 9.266 ≈ 70 mm²
4/0 107 11.68 ≈ 95–120 mm²

Rule of thumb: dropping 3 AWG numbersdoubles the area. And a smaller AWG number means a thicker wire — the opposite of what beginners expect.


2. Current-carrying capacity (ampacity) — copper, PVC insulation

The figure depends on the installation method — a cable buried in an insulated wall can't shed heat the way one hanging in free air can.

Area (mm²) In conduit, insulated wall (A1) In conduit on a wall (B1) Clipped direct (C) Free air (E)
1.5 14.5 A 17.5 A 19.5 A 22 A
2.5 19.5 A 24 A 27 A 30 A
4 26 A 32 A 36 A 40 A
6 34 A 41 A 46 A 51 A
10 46 A 57 A 63 A 70 A
16 61 A 76 A 85 A 94 A
25 80 A 101 A 112 A 119 A
35 99 A 125 A 138 A 147 A
50 151 A 168 A 179 A
70 192 A 213 A 229 A
95 232 A 258 A 278 A

Reference conditions: two loaded conductors, 30 °C ambient, PVC insulation (70 °C rating).

Derating factors — don't skip these

Condition Multiply the ampacity by
40 °C ambient 0.87
50 °C ambient 0.71
2 cables grouped 0.80
4 cables grouped 0.65
6 cables grouped 0.57

⚠️ Relevant in Syria: summer ambient passes 40 °C easily. A 2.5 mm² cable "rated 24 A" is really 21 A at 40 °C — and less again if it shares a conduit with other cables.


3. Conductor resistance (ohms per kilometre at 20 °C)

You need this for voltage-drop and heat-loss maths.

Area (mm²) Copper (Ω/km) Aluminium (Ω/km)
1.5 12.1
2.5 7.41
4 4.61 7.41
6 3.08 4.61
10 1.83 3.08
16 1.15 1.91
25 0.727 1.20
35 0.524 0.868
50 0.387 0.641
70 0.268 0.443
95 0.193 0.320
120 0.153 0.253
150 0.124 0.206
185 0.0991 0.164
240 0.0754 0.125

Aluminium needs roughly one size larger for the same current (resistivity 0.0282 vs 0.0175 Ω·mm²/m for copper) — but it's cheaper and lighter, which is why big feeders use it.

Temperature correction: resistance rises ≈ 0.4 % per °C. At 70 °C (a fully loaded cable) it is about 20 % higher than the table value.


4. Wire colours

The modern system (IEC 60445 — current standard)

Function Colour
Phase L1 Brown
Phase L2 Black
Phase L3 Grey
Neutral (N) Blue
Earth (PE) Green/yellow striped

Legacy systems you may still meet

System Phase Neutral Earth
Old UK Red Black Green
US Black / red White Green or bare

⚠️ Never trust colour alone. In old installations a blue conductor may well be live. Always measure before you touch.


5. Choosing a cross-section — four steps

  1. Work out the current: I = P / V (single phase) or I = P / (√3 × V × cos φ) (three phase).
  2. Read the ampacity table for a size that carries it — after applying the derating factors (ambient + grouping).
  3. Check the voltage drop: keep it ≤ 3 % for lighting and 5 % for power. Long runs are governed by voltage drop, not by current.
  4. Check the protection: the breaker rating must sit between the load and the cable: I_load ≤ I_breaker ≤ I_cable.

The classic mistake: sizing from the ampacity table alone and forgetting voltage drop. Over a 60 m run a 2.5 mm² cable "carries" 24 A — but the voltage drop will make the installation unusable.


Work it out yourself

Voltage drop and the minimum cross-section — enter the load and the distance:

voltage-drop

Current from power (to start step 1 above):

power-energy

Expensive, common mistakes

Mistake What it costs you
Ignoring summer ambient The cable runs over its limit → insulation cracks within a few years
Cramming a conduit full Cables heat each other → up to 40 % of capacity lost
Breaker bigger than the cable The cable burns before the breaker trips — the most dangerous error there is
Aluminium at copper sizes Overheating and excessive voltage drop
Forgetting the return path Voltage drop is calculated over there and back, not the one-way length

Key points

  • Smaller AWG = thicker wire. Three sizes down ≈ double the area.
  • Ampacity is not a single number — it depends on installation, ambient and grouping.
  • Voltage drop rules long runs; current rules short ones.
  • The breaker protects the cable before it protects the appliance.
كابلات اسلاك مقطع امبير هبوط جهد الوان الاسلاك AWG cables wire awg ampacity cross-section voltage drop IEC 60364 derating مرجع reference